May 05, 2016 0 Comments
The function of a cooling system is to remove heat from processes or equipment, Heat removed from one medium is transferred to another medium, or process fluid. Most often, the cooling medium is water. However, the heat transfer concepts and calculations discussed in this chapter can also be applied to other fluids.
Efficient removal of heat is an economic requirement in the design and operation of a cooling system. The driving force for the transfer of heat is the difference in temperature between the two media. In most cooling systems, this is in the range of 10—200 °F. The heat flux is generally
low and in the range of 5,000 to 15,000 Btu/ft2/hr. For exceptional cases such as the indirect cooling of molten metal, the heat flux can be as high as 3,000,000 Btu/ft2/hr.
The transfer of heat from process fluids or equipment results in a rise in temperature, or even a change of state, in the cooling water. Many of the properties of water, along with the behavior of the contaminants it contains, are affected by temperature. The tendency of a system to corrode, scale, or support microbiological growth is also affected by water temperature. These effects, and the control of Conditions that foster them, are addressed in subsequent chapters.
TYPES OF SYSTEMS
Water heated in the heat exchange process can be handled in one of two ways. The water can be discharged at the increased temperature into a receiving body (once-through cooling system), or it can be cooled and reused (recirculating cooling system).
There are two distinct types of systems for water cooling and reuse: open and closed recirculating systems. In an open recirculating system, cooling is achieved through evaporation of a fraction of the water. Evaporation results in a loss of pure water from the system and a concentration of the remaining dissolved solids. Water must be removed, or blown down, in order to control this concentration, and fresh water must then be added to replenish the system.
A closed recirculating system is actually a cooling system within a~ cooling system. The water containing the heat transferred from the process is cooled for reuse by means of an exchange with another fluid. Water losses from this type of system are usually small.
Each of the three types of cooling systems once—through, open recirculating, and closed recirculating—is described in detail in later chapters. The specific approach to designing an appropriate treatment program for each system is also contained in those chapters.
HEAT TRANSFER ECONOMICS
In the design of a heat transfer system, the capital cost of building the system must be weighed against the ongoing cost of operation and maintenance. Frequently, higher capital costs (more exchange surface, exotic metallurgy, more efficient tower fill, etc.) result in lower operating and maintenance costs, while lower capital costs may result in higher operating costs (pump and fan horsepower, required maintenance, etc). One important operating cost that must be considered is the chemical treatment required to prevent process or waterside corrosion, deposits and scale, and microbiological fouling. These problems can adversely affect heat transfer and can lead to equipment failure.
Heat Transfer
The following is an overview of the complex considerations involved in the design of a heat exchanger. Many texts are available to provide more detail.
In a heat transfer system, heat is exchanged as two fluids of unequal temperature approach equilibrium A higher temperature differential - results in a more rapid heat transfer.
However, temperature is only one of many factors involved in exchanger design for a dynamic system. Other considerations include the area over which heat transfer occurs, the characteristics of the fluids involved, fluid velocities, and the characteristics of the exchanger metallurgy.
Process heat duty, process temperatures, and available cooling water supply temperature are usually specified in the initial stages of design. The size of the heat exchanger(s) is calculated accordingly with important parameters such as process and water flow velocity, type of shell, layout of tubes, baffles, metallurgy, and fouling tendency of the fluids.
Factors in the design of a heat exchanger are related by the heat transfer equation:
Q = UAΔTm
Where
Q = rate of heat transfer (Btu/hr)
U = heat transfer coefficient (Btu/hr/ft2/°F)
A = heat transfer surface area (ft2)
ΔTm = log mean temperature difference between fluids (ft2)
The heat transfer coefficient, U, represents the thermal conductance of the heat exchanger. The higher the value of U, the more easily heat is transferred from one fluid to the other. Thermal conductance is the reciprocal of resistance, R, to heat flow.
U = 1/R
The total resistance to heat flow is the sum of several individual resistances. This is shown in the following figure and mathematically expressed below.
R1 = r1 + r2 + r3 + r4 + r5
Where
R1 = total heat flow resistance
r1 = heat flow resistance of the process-side film
r2 = heat flow resistance of the process-side fouling (if any)
r3 = heat flow resistance of the exchanger tube wall
r4 = heat flow resistance of the water-side fouling (if any)
r5 = heat flow resistance of the water-side film
The heat flow resistance of the process film and the cooling water film depends on equipment geometry, flow velocity, viscosity, specific heat, and thermal conductivity. The effect of velocity on heat transfer for water in a tube is shown in following figure.
Heat flow resistance due to fouling varies tremendously depending on the characteristics of [he fouling layer, the fluid, and the contaminants in the fluid that created the fouling layer. A minor amount of fouling is generally accommodated in the exchanger design. However, if fouling is not kept to a minimum, the resistance to heat transfer will increase, and the U coefficient will decrease to the point at which the exchanger cannot adequately control the process temperatures. Even if this point is not reached, the transfer process is less efficient and potentially wasteful. The resistance of the tube to heat transfer depends on the material of construction only and does not change with time. Tube walls thinned by erosion or corrosion may have less resistance, but this is not a significant change.
The log mean temperature difference (ΔTm) is a mathematical expression addressing the temperature differential between the two fluids at each point along the heat exchanger.
When there is no change in state of the fluids, a countercurrent flow exchanger is more efficient for heat transfer than a concurrent flow exchanger. Therefore, most coolers operate with a countercurrent or a variation of countercurrent flow. Calculated ΔTm formulas may be corrected for exchanger configurations that are not truly countercurrent.
February 28, 2024 0 Comments
February 28, 2024 0 Comments
April 19, 2023 0 Comments